SPM Online-UPS 15KVA RT Long Model 220V China 3: 3 or 3:1
Input specifications
Note: The voltages in the above table are Single Phase (Ph - N) values. The corresponding Three Phase
value will be √3 times the Single Phase value
Output specifications
Nominal input voltage 220 VAC (Ph - N)
Input frequency 50/60 Hz nominal
Input voltage range (100% load) - Single Phase
Power gets derated to 50%
176 to 275 VAC (Ph - N)
275 to 300 VAC (Ph - N)
Input voltage range (80% load) 150 to 300 VAC (Ph - N)
Input voltage range (50% load) 110 to 300 VAC (Ph - N)
Input power factor (100% resist
Output specifications
SPM10KL-33 SPM15KL-33 SPM20KL-33
UPS Capacity Battery Voltage = ±96 VDC 10 kVA / 8 kW 15 kVA / 12 kW 20 kVA /
16 kW
Battery Voltage = ±108 VDC 10 kVA / 9 kW 15 kVA / 13.5 kW 20 kVA / 18 kW
Battery Voltage = ±120 VDC 10 kVA / 10 kW 15 kVA / 15 kW 20 kVA / 20 kW
Nominal output voltage
220/380 VAC
Other programmable voltage 230/400 VAC,
240/415 VAC
Efficiency at rated load
95%
Output voltage regulation ±1% of
initial value
Output voltage distortion • < 2% for full linear load
• < 4% for full non linear load
• < 15% for the last 60 seconds of the backup time
Frequency - On battery
50/60 Hz ± 0.5%
Frequency - AC mode
50/60 Hz ± 3 Hz
Crest factor
3:1
Waveform
Sinewave
Output connection Refer "Rear panel features"
on page 11 for details
Bypass
Internal
Bypass range 185 -
250 VAC ± 1% (Ph - N)
320 - 433 VAC ± 1% (Ph - Ph)