Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | Standby |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
•Compact size
•Excellent microprocessor control guarantees high reliability
•Boost and buck AVR for voltage stabilization
•Auto restart while AC is recovering
•Simulated sine wave
•Off-mode charging
•Cold start function
•Generator compatible
MODEL | 1K (L) | 2K(L) | 3K(L) | 6K (L) | 10K (L) | |||||||
PHASE | Single phase with ground | |||||||||||
CAPACITY* | 1000 VA/800 W | 2000 VA/1600 W | 3000 VA/2400 W | 6000VA/4800W | 10000 VA/8000 W | |||||||
INPUT | ||||||||||||
Nominal Voltage | 110/115/120/127VAC or 208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
Input Voltage Range | 55-150 VAC or 110-300 VAC(Based on load at 50%) 85-140VAC or 160-280VAC(Based on load at 100%) |
110-300 VAC (Based on load at 50%) 176-300 VAC(Based on load at 100%) |
||||||||||
Frequency Range | 40 Hz ~70 Hz | 46~54 Hz or 56~64 Hz | ||||||||||
Power Factor | ≥0.99@Nominall Voltage (100%load) | |||||||||||
OUTPUT | ||||||||||||
Output Voltage | 110/115/120/127VAC or 208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
Voltage Regulation | ±1% | |||||||||||
Frequency Range(Synchronized Range) | 47~53 Hz or 57~63 Hz | 46~54 Hz or 56~64 Hz | ||||||||||
Frequency Range (Batt.Mode) | 50 Hz±0.25 Hz or 60Hz±0.3 Hz | 50 Hz or 60Hz±0.1 Hz | ||||||||||
Current Crest Ratio | 3:1 | |||||||||||
Harmonic Distortion | ≤3%THD (Linear Load) ≤6%THD (Non-linear Load) |
≤3%THD (Linear Load) ≤5%THD (Non-linear Load) |
||||||||||
Transfer Time |
AC Mode to Battery Mode | Zero | ||||||||||
Inverter to Bypass | 4 ms(Typical) | Zero | ||||||||||
Waveform(Batt.Mode) | Pure Sinewave | |||||||||||
EFFICIENCY | ||||||||||||
AC Mode | 88% | 89% | 90% | 92% | 93% | |||||||
Battery Mode | 83% | 87% | 88% | 90% | 91% | |||||||
BATTERY | ||||||||||||
Standard Model |
Battery Type | 12V/9 Ah | 12V/9 Ah | 12V/9 Ah | 12V/9 Ah | |||||||
Numbers | 2 | 4 | 6 | 16 | 20 | 16 | 20 | |||||
Typical Recharge Time | 4 hours recover to 90%capacity | 9 hours recover to 90%capacity | ||||||||||
Charging Current(max.) | 1A | 1A/2A | ||||||||||
Charging Voltage | 27.4VDC±1% | 54.7 VDC±1% | 82.1 VDC±1% | 218.4 VDC±1% | 273VDC±1% | |218.4 VDC±1% | 273VDC±1% | |||||
Long-run Model** |
Battery Type | Depending on the capacity of external batteries | ||||||||||
Numbers | 2 | 3 | 4 | 6 | 8 | 6 | 8 | 16~20 (Adjustable) | ||||
Charging Current(max.) | 1A/2A/4A/6A(Adjustable) | 1A/2A/4A6A(Adjustable,6A is only available for 16pcs batteries) | ||||||||||
Charging Voltage | 27.4VDC±1%41.0VDC±1% | 54.7VDC±1%82.1 VDC±1%|109.4VDC±1%82.1 VDC±1%|109.4VDC±1% | 273 VDC±1%(Based on 20pcs batteries) | |||||||||
INDICATORS | ||||||||||||
LCD | Load level,Battery level,AC mode,Battery mode,Bypass mode,and Fault indicators | |||||||||||
ALARM | ||||||||||||
Battery Mode | Sounding every 4 seconds | |||||||||||
Low Battery | Sounding every second | |||||||||||
Overload | Sounding twice every second | |||||||||||
Fault | Continuously sounding | |||||||||||
PHYSICAL | ||||||||||||
Standard Model |
Dimension,DxWxH(mm) | 282×145×220 | 397×145×220 | 421×190×318 | 369×190×688 | 442×190×688 | ||||||
Net Weight(kgs) | 9.8 | 17 | 27.6 | 61 | 74 | 66 | 76 | |||||
Long-run Model** |
Dimension,DxWxH(mm) | 282×145×220 | 397x145×220 | 369x190×318 | 442×190x318 | |||||||
Net Weight(kgs) | 4.1 | 6.8 | 7.4 | 12 | 16 | |||||||
ENVIRONMENT | ||||||||||||
Humidity | 20-90%RH@0-40ºC(Non-condensing) | 0-95%RH @0-50°ºC (non-condensing) |
0-95%RH @0-40°ºC (non-condensing) |
|||||||||
Noise Level | Less than 50dB@1 Meter | Less than 55dB @1 Meter | Less than 58dB @1 Meter | |||||||||
MANAGEMENT | ||||||||||||
Smart RS-232/USB | Supports WindowsR Family,Linux and MAC | |||||||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||||||
*1-3KVA:Derate to 80%of capacity in Frequency converter mode and to 80%when the output voltage is adjusted to 208VAC. 6-10KVA:Derate to 60%of capacity in Frequency converter mode and to 90%when the output voltage is adjusted to 208VAC **Long-run model is only available for 208/220/230/240VAC systems. Product specifications are subject to change without further notice. |