MODEL | A+42U-300 (PM-50)S | A+42U-300(PM-50) | A+42U-350(PM-50) | A+42U-400(PM-50) | A+42U-500(PM-50) |
PHASE | 3-phase in/3-phase out | ||||
CABINETCAPACITY* | 300KW | 300KW | 350KW | 400KW | 500KW |
BATTERY TYPE | External Battery | ||||
ONE POWERMODULECAPACITY | 50KVA/50KW | ||||
MAX.POWER MODULENO. | 6 | 6 | 7 | 8 | 10 |
INPUT | |||||
Nominal Voltage | 3×380/400/415 VAC (3Ph+N) | ||||
Voltage Range | -20%~+15% | ||||
Nominal Frequency | 50/60Hz (Auto Sensing) | ||||
Frequency Range | 40Hz~70Hz | ||||
Power Factor | >0.99@100%Load,>0.98@50%Load | ||||
Harmonic Distortion (THDi) | <4%@100%load | ||||
OUTPUT | |||||
Nominal Voltage | 3x380/400/415 VAC (3Ph+N) | ||||
Voltage Regulation(Steady state) | ≤±1%Typical (balanced load);≤±2%Typical (unbalanced load) | ||||
Nominal Frequency | 50/60Hz | ||||
Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz | ||||
Overload Capability | 1 hour for≤110%,10 mins for 111%~125%,1 min for 126%~150%and 200ms for>150% | ||||
Harmonic Distortion | ≤2%THD (Linear Load);≤4%THD (Non-linear Load) | ||||
Efficiency | 96% | ||||
BATTERYICHARGER | |||||
Nominal Voltage | +/-192V~+/-240V(Selectable) | ||||
Maximum Voltage | +/-240V (12Vx40 Pcs) | ||||
Minimum Voltage | +/-192V (12V×32 Pcs) | ||||
Floating Charge Voltage | 2.28V/Cell(2.25~2.33 Selectable) | ||||
Boost Charging Voltage | 2.35V/Cell | ||||
Temperature Compensation | Yes | ||||
Maximum Charging Current (Per Power Module) |
12A(Adjustable) | ||||
PHYSICAL | |||||
Cabinet Dimension (DxWxH)mm | 850×600x2000 | 1065×600×2010 | 1100×600×2010 | 1100×600×2010 | 1065x1000×2000 |
Net Weight (Kg) | 490 | 545 | 654 | 932 | 1020 |
ENVIRONMENT | |||||
Operating Temperature | 0~40ºC | ||||
Relative Humidity | 0~95%non-condensing | ||||
Altitude* | <1000m for Nominal power | ||||
IP Protection | IP 20 | ||||
MANAGEMENT | |||||
Smart RS-232/USB | Supports WindowsR Family,Linux and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
STANDARDS | |||||
Safety | IEC/EN 62040-1 | ||||
EMC | IEC/EN 62040-2 Category C3 | ||||
***f the UPS is instlled or used in a placewhere the altiude is above than 1000m,the output power must be derated one percent per 100m Product specifications are subject to change without further notice. |