All units adopt modular design, including power module, bypass module, monitoring module, and can be easily integrated in MDC or customized cabinet.
Power module, bypass module, monitoring module, and ECU control module are all hot-swappable.
Wide input voltage range: line voltage range is 138-485V; UPS derates to 40% when input voltage is below 305V.
Multiple digital bus and redundancy parallel control system ensure the system remains online if any single circuit fails.
UPS continues operating in single or parallel mode if any module fails.
Thickened conformal coating for harsh environments (high heat, high humidity, dust, salt spray).
High input power factor (up to 0.99).
3-level topology design with efficiency up to 96%.
THDi < 3% (100% linear load).
UPS enters sleeping mode under very small loads.
Enables 2 independent UPS systems to work in synchronization, enhancing system reliability.
Supports parallel expanded operation (maximum 8 units).
Supports shared batteries for parallel UPS systems.
Battery count per group selectable from 30 to 50 pieces.
Large charging current supports long backup time requirements.
Output power factor of 1.0; can supply 100% unbalanced load.
High load adaptability: compatible with full inductive or capacitive loads.
7-inch (standard) or 10-inch (optional) colorful touch LCD screen.
Supports recording and exporting history logs and fault logs.
Interfaces: SNMP, RS232, RS485, dry contact.
Supports online FW & SW upgrades.
EPO & REPO function.
Power Walk-in function reduces start current impact on the system and lowers generator capacity requirements.
Module Model YMK3300-RM-40 | YMK3300-RM-50 | ||
Cabinet Model | YMK3300-120/200/300 | YMK300-200/300/400/500/600/800/1000 | |
Cabinet capacity | 200kVA | 200kVA~1000kVA | |
Module capacity | 40kVA 50kVA | ||
Max.number | 5/8 | 4/6/8/10/12/16/20 | |
INPUT | |||
Nominal voltage | 380/400/415Vac,(3Ph+N+PE) | ||
Operating voltage range | 138~305Vac for40%load;305~485Vac for 100%load | ||
Operating frequency range | 40Hz~70Hz | ||
Power factor | ≥0.99 | ||
Harmonic distortion(THDi) | ≤3%(100%linear load) | ||
Bypass voltage range | Max.voltage:220V:+25%(Optional+10%,+15%,+20%) 230V:+20%(Optional+10%,+15%) 240V:+15%(Optional +10%) Min.voltage:-45%(Optional-10%,-15%,-20%,-30%) |
||
Bypass frequency range | Frequency protection range:±10% | ||
Power walk in | Support | ||
Generator input | Support | ||
OUTPUT | |||
Rated voltage | 380/400/415Vac,(3Ph+N+PE) | ||
Power factor | 1.0 | ||
Voltage regulation | ±1% | ||
Output Line mode | Synchronize with input,when the input frequency>±10%(±1%/±2%/±4%/±5%optional),output 50/60(±0.1Hz) | ||
frequency Bat.mode | (50/60±0.1%)Hz | ||
Crest factor | 3:1 | ||
Harmonic distortion(THDv) | ≤1%with linear load;≤3%with nonlinear load | ||
Efficiency | up to 96% | ||
BATTERY | |||
Battery voltage | ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs,36pcs default, 36~50pcs output power factor 1.0,32~34pcs output power factor 0.9,30pcs output power factor 0.8) |
||
Powermodule charge cument | 20A(Max.) | ||
SYSTEM FEATURES | |||
Transfer time | Utility to Battery:Oms;Utility to Bypass:Oms | ||
Overload | Inverter mode | ≤110%60min,≤125%10min,≤150%1min,>150%1.2s shut down inverter | |
Bypass mode | 30ºC:135%for long term;40ºC:125%for long term;>1000%,100ms | ||
Overheat | Line Mode:Switch to Bypass;Backup Mode:Shut down UPS immediately | ||
Low battery voltage | Alarm and Switch off | ||
Self-diagnostics | Upon Power On and Software Control | ||
Backfeed protection | Support | ||
EPO(Optional) | Shut down UPS immediately(Turn to bypass optional) | ||
Battery | Advanced Battery Management | ||
Noise suppression | Complies with EN62040-3 | ||
Audible &visual alarms | Line Failure,Battery Low,Overload,System Fault | ||
Status LED&LCD display | Line Mode,Bypass Mode,Battery Low,Battery Fault,Overload &UPS Fault | ||
Reading on the LCD display | Input,Output,Battery,Command,Setting,Maintenance | ||
Communication interface | RS232,RS485,Parallel,LBS,Dry contact port,Relay card(Optional),SNMP card(Optional),Battery temperature sensor(Optional) | ||
ENVIRONMENTAL | |||
Operating temperature | 0ºC~40ºC | ||
Storage temperature | -25ºC~55ºC | ||
Humidity range | 0~95%(Non condensing) | ||
Altitude | <1500m,derating required when>1500m | ||
Noise level | <68dB | <73dB | |
PHYSICAL | |||
Dimension W×D×H |
UPS cabinet (S/F) |
200/320kVA:600×850×2000mm | 200/300/400kVA:600×850×2000mm 500/600kVA:1200×850×2000mm 800/1000kVA:2000×850×2000mm |
Power module | 440×620×130mm | ||
Net weight | UPS cabinet (S/F) |
200KVA:210kg;320kVA:270kg | 200kVA:240kg;300kVA:260kg;400kVA:290kg; 500kVA:480kg;600kVA:540kg;800kVA:960kg; 1000kVA:1050kg |
Power module | 33kg | 34kg | |
STANDARDS | |||
Safety | IEC/EN 62040-1,IEC/EN 62477-1 | ||
EMC | IECEN62040-2(IEC61000-2-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,EC61000-4-8,IEC61000-4-11) |