Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | Standby |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
We supply various products from China to many African companies that participate in tenders, contracts, and projects such as hospitals, airports, schools, metros, and data centers.
Focus on UPS power, Solar Products, EV Charging Stations, Voltage stabilizers, lithium/Lead-acid Batteries, Precision air conditioners, and Power distribution Cabinets.
MODEL | Giant 10K | Giant 15K | Giant 20K | Giant 30K | Giant 40K | Giant 60K | Giant 80K | Giant 100K | Giant 120K | Giant 160K | Giant 200K | |
CAPACITY | 10 KVA/ 8 KW |
15KVA/ 12KW |
20 KVA/ 16 KW |
30 KVA/ 24 KW |
40 KVA/ 32 KW |
60 KVA/ 48 KW |
80 KVA/ 64 KW |
100 KVA/ 80 KW |
120 KVA/ 96KW |
160 KVA/ 128KW |
200 KVA/ 160KW |
|
INPUT | ||||||||||||
Nominal Voltage | 3×380VAC/400VAC (3Ph+N) | |||||||||||
Acceptable Voltage Range | 285VAC~475VAC | |||||||||||
Frequency | 50/60 Hz±10% | |||||||||||
INVERTER | ||||||||||||
Nominal Voltage | 3×380VAC/400VAC (3Ph+N) | |||||||||||
Precision | Stationary:±1% Transitory:±5%(load variations 100-0-100%) |
|||||||||||
Frequency | 50/60 Hz synchronised±1% With mains absent±0.1 Hz |
|||||||||||
Max.Synchronization Speed | ±1 Hz/s | |||||||||||
Waveform | Pure Sinewave | |||||||||||
Total Harmonic Distortion (THDv) |
<2%(Linear Load);<5%(Non-linear Load) | |||||||||||
Phase Displacement | 120°±1%(balanced load);120°±2%(imbalances 50%of the load) | |||||||||||
Dynamic Recovery Time | 3 cycles at 90%of the static value | |||||||||||
Admissible Overload | 110%for 10min;150%for 60sec;>160%for 200ms | |||||||||||
Admissible Crest Factor | 3:1 | |||||||||||
Admissible Power Factor | 0.6~1 (inductive or capacitive) | |||||||||||
Imbalance Output Voltage @100%Unbalanced Load |
<1% | |||||||||||
Current Limit | High overload,short-circuit:RMS Voltage Limit High Crest-Factor current:Peak Voltage Limit |
|||||||||||
STATIC BYPASS | ||||||||||||
Type | Solid state | |||||||||||
Voltage | 3×380VAC/400VAC (3Ph+N) | |||||||||||
Frequency | 50/60 Hz | |||||||||||
Activation Criterion | Microprocessor control | |||||||||||
Transfer Time | Zero | |||||||||||
Admissible Overload | 150%for 1 hour;180%for 30sec;>200%for 200ms | |||||||||||
Transfer to Bypass | Immediate,for overloads above 160% | |||||||||||
Retransfer | Automatic after alarm clear | |||||||||||
MAINTENANCE BYPASS | ||||||||||||
Type | Without interruption | |||||||||||
Voltage | 3×400V (3Ph+N) | |||||||||||
Frequency | 50/60 Hz | |||||||||||
Overall Efficiency |
Line Mode | 89% | 90% | 91% | 92% | |||||||
Battery Mode | 90% | 91% | 92% | 93% | ||||||||
BATTERY&CHARGER | ||||||||||||
Battery Type and Numbers | 12VDC×32 pcs (29~32 pcs adjustable) | |||||||||||
Nominal Battery Voltage | 384 VDC(Based on 32pcs batteries) | |||||||||||
Charging Method | CC/CV | |||||||||||
Precision | ±1% | |||||||||||
Charging Current | Default 10A,*Maximum= Capacity(KW)/Battery (real-time). |
Default 10A;Maximum 40A;5A@full load | ||||||||||
Charging Voltage | 432 VDC (Based on 32pcs batteries) | |||||||||||
PHYSICAL | ||||||||||||
Dimensions,DxWxH(mm) | 656×405×817 | 656×405 x941 |
821x432x1159 | 975×554×1286 | 975×554x 1326 |
1051×705×1646 | ||||||
Net Weight(Kgs) | 118 | 120 | 145 | 193 | 278 | 365 | 471 | 573 | 650 | 760 | 840 |