| Customization: | Available |
|---|---|
| Phase: | Single Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
True double-conversion
DSP technology guarantees high reliability
N+X parallel redundancy
Selectable quantity of battery for each group:16/18/20 pieces
Adjustable charging current via LCD
3-stage charging design optimizes battery performance
ECO mode operation for energy saving
Self-diagnosis at startup
Emergency power off function(EPO)
Maintenance bypass is convenient for maintenance
Generator compatible
Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
Cold start
| MODEL | UDC S 6K | UDC H 6K | UDC S 10K | UDC H 10K | ||
| Capacity (VA/Watts) | 6K / 5.4K | 10K / 9K | ||||
| INPUT | ||||||
| Nominal Voltage | 220/230/240Vac(L+N+PE) | |||||
| Operating Voltage Range | 120Vac-276Vac | |||||
| Operating Frequency Range | 50Hz:45~55Hz,60Hz:54~66Hz | |||||
| Power Factor | ≥0.99 | |||||
| Bypass Voltage Range | Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||||
| 230V:+20%(Optional +10%,+15%) | ||||||
| 240V:+15%(Optional +10% ) | ||||||
| Min. voltage: -45% (Optional -20%,-30%) | ||||||
| ECO Range | Same as bypass | |||||
| Harmonic Distortion (THDi) | ≤5%(100% non-linear load) | |||||
| OUTPUT | ||||||
| Output Voltage | 220/230/240Vac | |||||
| Power Factor | 0.9 | |||||
| Voltage Regulation | ±1% | |||||
| Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) | ||||
| Bat. Mode | (50/60±0.1)Hz | |||||
| Crest Factor | 3:1 | |||||
| Harmonic Distortion (THDv) | ≤2% with linear load | |||||
| ≤5% with non-linear load | ||||||
| Waveform | Pure Sinewave | |||||
| Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||||
| EFFICIENCY | ||||||
| Efficiency | Up to 94% | |||||
| BATTERY | ||||||
| Battery Voltage | Selectable Voltage: ±96/108/120Vdc | |||||
| Typical Recharge Time | 6-8 hours (To 90% capacity) | |||||
| Charging Current | Maximum current 10A | |||||
| PROTECTION | ||||||
| Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode | ||||
| Bypass Mode | 40A(Input breaker) | 60A(Input breaker) | ||||
| Short Circuit | Hold Whole System | |||||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||
| Battery Low | Alarm and Switch off | |||||
| INDICATORS | ||||||
| Audible & Visual Alarms | Line Failure, Battery Low, Overload, System Fault | |||||
| Status LED & LCD Display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault | |||||
| Parameters On The LCD Panel | Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time |
|||||
| MANAGEMENT | ||||||
| Communication Interface | RS-232,USB,Parallel card(Optional), SNMP card(Optional), Relay card (Optional) | |||||
| ENVIRONMENT | ||||||
| Operating Temperature | 0ºC~40ºC | |||||
| Storage Temperature | -25ºC~55ºC | |||||
| Humidity Range | 0~95% (Non-condensing) | |||||
| Altitude | < 1500m | |||||
| Noise Level | <55dB | |||||
| PHYSICAL | ||||||
| Dimension W×D×H (mm) | 250×502×616 | 220×481×438 | 250×502×616 | 220×481×438 | ||
| Net Weight (kg) | 62 | 18 | 64 | 20 | ||
| STANDARDS | ||||||
| Noise Suppression | Complies with EN62040-2 | |||||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||||
| IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||||
| BATTERY PACK | ||||||
| Model | EXB±120V | |||||
| Battery type& Max.quantity | 7Ah×40/9Ah×40 | |||||
| Dimensions W×D×H (mm) | 250×502×616 | |||||
| Net Weight (kg) | 125.8/138 | |||||