Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | Standby |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
We supply various products from China to many African companies that participate in tenders, contracts, and projects such as hospitals, airports, schools, metros, and data centers.
Focus on UPS power, Solar Products, EV Charging Stations, Voltage stabilizers, lithium/Lead-acid Batteries, Precision air conditioners, and Power distribution Cabinets.
MODEL | Power 30U-90HV | Power 42U-120HV | Power 30U-120HV Power 30U-80-20KHV |
Power 30U-180HV +ower 30U-120-20KHV |
Power 42U-200-20KHV |
Power 42U-210HV | Power 42U-300HV | |
PHASE | 3-phase in/3-phase out | |||||||
CABINET CAPACITY* | 90 KW | 120 KW | 120 KWor 80 KW | 180 KWor 120 KW | 200 KW | 210 KW | 300 KW | |
BATTERY TYPE | Built-in Battery | External Battery | ||||||
ONE POWER MODULE CAPACITY | 30KVA/30KW | 30KVA/30KW or 20KVA/20KW | 20KW | 30KVA/30KW | 30KVA/30KW | |||
MAX.POWER MODULENO. | 3 | 4 | 4 | 6 | 10 | 8 | 10 | |
MAX.BATTERY SETNO.** | 3 | 5 | - | - | - | - | - | |
INPUT | ||||||||
Nominal Voltage | 3×380VAC/400VAC/415VAC (3Ph+N) | |||||||
Voltage Range | 305~478 VAC at 100%load;208~478VAC at <70%load | |||||||
Nominal Frequency | 50/60Hz(Auto Sensing) | |||||||
Frequency Range | 40Hz~70Hz | |||||||
Power Factor | >0.99@100%Load,>0.98@50%Load | |||||||
Harmonic Distortion(THDi) | <3%@100%load |
|||||||
OUTPUT | ||||||||
Nominal Voltage | 3×380VAC/400VAC/415VAC (3Ph+N) | |||||||
Voltage Regulation(Steady state) | ≤±1%Typical (balanced load);≤±2%Typical (imbalanced load) | |||||||
Nominal Frequency | 50/60Hz | |||||||
Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz | |||||||
Overload Capability | 1 hour for 110%,10 mins for 125%,;1 min for 150%,200ms for>150% | |||||||
Harmonic Distortion | ≤2%THD (Linear Load);≤4%THD (Non-linear Load) | |||||||
Efficiency | Up to 94.5% | |||||||
BATTERYICHARGER | ||||||||
Nominal Voltage | +/-216V(12V×36 pcs) | |||||||
Maximum Voltage | +/-240V(12V×40 pcs) | |||||||
Minimum Voltage | +1-192V(12V×32 pcs) | |||||||
Float Charging Voltage | 2.25V/Cell | |||||||
Boost Charging Voltage | 2.35V/Cell | |||||||
Temperature Compensation | Yes | |||||||
Maximum Charging Current (Per Power Module) |
8A | 8A for 30KW power module 6A for 20KW power module |
6A | 8A | ||||
PHYSICAL | ||||||||
Cabinet Dimension(DxWxH)mm | 1100×600×1475 | 1100x600×2010 | 1100×600×1475 | 1100x600×1475 | 1100×600×2010 | |||
Net Weight (Kg) | 675 | 932 | 335 or 333 | 437.5 or 434.5 | 611 | 549 | 620 | |
ENVIRONMENT | ||||||||
Operating Temperature | 0~40ºC | |||||||
Relative Humidity | 0~95%non-condensing | |||||||
Altitude | <1000m for Nominal power | |||||||
IP Protection | IP 20 | |||||||
MANAGEMENT | ||||||||
Smart RS-232/USB | Supports WindowsR Family,Linux and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||
STANDARDS | ||||||||
Safety | IEC/EN 60950-1;IEC/EN 62040-1 | |||||||
EMC | IEC/EN 62040-2 Category C3 | |||||||
*When temperature is above 30ºC,the output power factor will be de-rated,0.9 at 31ºC~35ºCand 0.8 at 36ºC~40ºC. | ||||||||
**One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray.One complete battery set contains 4 battery modules. **f the UPS is instlled or used in a place where the alitude is above than 1000m,the output power must be derated one percent per 100m. Product specifications are subject to change without further notice. |